Two-zone CO detection system, extendible to 3 with module FM-M509, mountedin ABS plastic casing, with possibility of recessed mounting. Each modulea
560973 FM-C502
Two-zone CO detection system, extendible to 3 with module FM-M509, mounted
in ABS plastic casing, with possibility of recessed mounting. Each module
allows connection of up to 32 detectors connected to 2 wires without polarity,
with a maximum distance of 1 km. The system has three programmable level
relays, extraction 1 and extraction 2 and alarm. The relays can be configured
to be activated with a fault. The system of algorithms has two operation types,
standard or by line sensing. The system has a test mode for maintaining the
installation. Optionally, the system can incorporate the cards FM-TC500 or
FM-TC501, which allow you to control a speed regulator connected to a motor,
making energy savings. Dimensions 439 x 268 x 112.